3C 500mm2 Al 6.35/11kV PVC Black
3C 500mm2 Al 6.35/11kV PVC Black
6.35/11kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJHA30AA003CXAA
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Construction
- Stranded compacted conductors
- Semi-conductive insulation screen
- Copper wire screen
- XLPE insulation
- Semi-conductive conductor screen
- PVC sheath
- Fillers
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
845.0 kg/100m
Conductor cross-section
500 mm²
Conductor diameter
26.5 mm
Diameter over insulation
34.66 mm
Diameter over screen
38.16 mm
Nominal Duct Diameter
150 mm
Nominal Screen Area on each core
68.09 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter
90.9 mm
Number of screen wires (nb x mm Ø)
40 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.082 Ohm/km
Capacitance (All Main Cores - Screen)
0.62 µF / km
Charging current per phase
1.24 A/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
31.4 W/km
Inductive reactance at 50Hz
0.085 Ohm/km
Insulation resistance at 20°C
3900 MOhm.km
Max. DC resistance of the conductor at 20°C
0.062 Ohm/km
Maximum electric stress
2 kV/mm
Permissible short circuit current conductor 1s
47.3 kA
Permissible short circuit current screen 1s
10.1 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.038 Ohm/km
Zero sequence resistance at 20°C
0.859 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
75 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1640 mm
Minimum Bend Radius - Installed
1090 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core
Current carrying capacity table (in Amps) - 6.35/11kV Three CoreConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
500.0 | 779.0 | 622.0 | 850.0 | 679.0 | 569.0 | 454.0 | 710.0 | 567.0 | 597.0 | 477.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |