3C 120mm2 Cu 19/33kV PVC Black

Description

Description

Standards

  • International
    IEC 60228; IEC 60502-2
  • National
    AS/NZS 1125; AS/NZS 1429.1

Construction

  • Stranded compacted conductor
  • Semi-conductive insulation screen
  • Copper wire screen
  • XLPE insulation
  • Semi-conductive conductor screen
  • FIllers
  • PVC sheath

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Armour type
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted

Dimensional characteristics

Dimensional characteristics

Approximate weight
765.0 kg/100m
Conductor cross-section
120 mm²
Conductor diameter
13.07 mm
Diameter over insulation
30.586 mm
Diameter over screen
33.886 mm
Nominal Duct Diameter
125 mm
Nominal Screen Area on each core
68.09 mm²
Nominal insulation thickness
8.0 mm
Nominal overall diameter
81.1 mm
Nominal overall diameter
Number of screen wires (nb x mm Ø)
40 x 0.85 mm Ø

Electrical characteristics

Electrical characteristics

A.C. Conductor resist. 50Hz and at 90 °C
0.196 Ohm/km
Capacitance (All Main Cores - Screen)
0.179 µF / km
Charging current per phase
1.068 A/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
81.1 W/km
Inductive reactance at 50Hz
0.123 Ohm/km
Insulation resistance at 20°C
14000 MOhm.km
Max. DC resistance of the conductor at 20°C
0.153 Ohm/km
Maximum electric stress
3.5 kV/mm
Permissible short circuit current conductor 1s
17.1 kA
Permissible short circuit current screen 1s
10.1 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.076 Ohm/km
Zero sequence resistance at 20°C
0.949 Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
25.2 kN

Usage characteristics

Usage characteristics

Minimum Bend Radius - During Installation (under Tension)
1460 mm
Minimum Bend Radius - Installed
970 mm

Resources

Resources

Current carrying capacity table (in Amps) - 19/33kV Three Core

Current carrying capacity table (in Amps) - 19/33kV Three Core
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al
120.0 352.0 272.0 377.0 292.0 271.0 210.0 341.0 264.0 290.0 224.0
In air touching (3 core)
In air spaced (3 core)
In air enclosed (3 core)
Underground Direct Buried (3 core)
Underground ducts (3 core)

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close