3C 240mm2 Cu 6.35/11kV SWA Red
3C 240mm2 Cu 6.35/11kV SWA Red
6.35/11kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJJP26AA003JBAA
- Country ref. : XJJP26AA003JBAA
- EAN : 99319215165294
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, laid-up, PVC bedded, steel wire armoured, PVC sheathed.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
Galvanized steel wires
Colour
Red
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
XLPE
Material of bedding
PVC
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
1470.0 kg/100m
Conductor cross-section
240 mm²
Conductor diameter
18.53 mm
Diameter over armour
75.0 mm
Diameter over insulation
26.6 mm
Diameter over screen
29.79 mm
Nominal Duct Diameter
125 mm
Nominal Screen Area on each core
68.09 mm²
Nominal armour wire diameter
3.15 mm
Nominal diameter over bedding
64.4 mm
Nominal insulation thickness
3.4 mm
Nominal overall diameter
82.3 mm
Number of screen wires (nb x mm Ø)
40 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.098 Ohm/km
Armour DC resistance at 20°C
0.293 Ohm/km
Capacitance (All Main Cores - Screen)
0.456 µF / km
Charging current per phase
0.913 A/km
DC Resistance of the Screen at 20°C
0.27 Ohm/km
Dielectric loss per phase
23.2 W/km
Inductive reactance at 50Hz
0.087 Ohm/km
Insulation resistance at 20°C
5300 MOhm.km
Max. DC resistance of the conductor at 20°C
0.075 Ohm/km
Maximum electric stress
2.1 kV/mm
Permissible short circuit current conductor 1s
34.3 kA
Permissible short circuit current screen 1s
10.1 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.111 Ohm/km
Zero sequence resistance at 20°C
0.495 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pull Tension of Armour
66 kN
Maximum Pull Tension of Conductor
50 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1480 mm
Minimum Bend Radius - Installed
990 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core SWA
Current carrying capacity table (in Amps) - 6.35/11kV Three Core SWAConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
240.0 | 495.0 | 391.0 | 534.0 | 422.0 | 373.0 | 296.0 | 469.0 | 372.0 | 396.0 | 315.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground Direct Buried (3 core) |
Underground ducts (3 core) |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania