3C 50mm2 Cu 6.35/11kV SWA Red
3C 50mm2 Cu 6.35/11kV SWA Red
6.35/11kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJJP19AA003JBAA
- Country ref. : XJJP19AA003JBAA
- EAN : 99319215164976
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, laid-up, PVC bedded, steel wire armoured, PVC sheathed.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
Galvanized steel wires
Colour
Red
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
XLPE
Material of bedding
PVC
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
565.0 kg/100m
Conductor cross-section
50 mm²
Conductor diameter
8.0 mm
Diameter over armour
50.2 mm
Diameter over insulation
16.1 mm
Diameter over screen
19.26 mm
Nominal Duct Diameter
100 mm
Nominal Screen Area on each core
49.37 mm²
Nominal armour wire diameter
2.5 mm
Nominal diameter over bedding
41.7 mm
Nominal insulation thickness
3.4 mm
Nominal overall diameter
55.7 mm
Number of screen wires (nb x mm Ø)
29 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.494 Ohm/km
Armour DC resistance at 20°C
0.559 Ohm/km
Capacitance (All Main Cores - Screen)
0.242 µF / km
Charging current per phase
0.488 A/km
DC Resistance of the Screen at 20°C
0.37 Ohm/km
Dielectric loss per phase
12.4 W/km
Inductive reactance at 50Hz
0.112 Ohm/km
Insulation resistance at 20°C
9900 MOhm.km
Max. DC resistance of the conductor at 20°C
0.387 Ohm/km
Maximum electric stress
2.5 kV/mm
Permissible short circuit current conductor 1s
7.1 kA
Permissible short circuit current screen 1s
7.32 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.139 Ohm/km
Zero sequence resistance at 20°C
1.051 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pull Tension of Armour
34 kN
Maximum Pull Tension of Conductor
10 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1000 mm
Minimum Bend Radius - Installed
670 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core SWA
Current carrying capacity table (in Amps) - 6.35/11kV Three Core SWAConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
50.0 | 195.0 | 152.0 | 208.0 | 162.0 | 150.0 | 117.0 | 201.0 | 157.0 | 165.0 | 129.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground Direct Buried (3 core) |
Underground ducts (3 core) |