3C 150mm2 Al 6.35/11kV SWA Red
3C 150mm2 Al 6.35/11kV SWA Red
6.35/11kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJJA24AA003JBAA
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, laid-up, PVC bedded, steel wire armoured, PVC sheathed.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
Galvanized steel wires
Colour
Red
Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Material of bedding
PVC
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
730.0 kg/100m
Conductor cross-section
150 mm²
Conductor diameter
14.17 mm
Diameter over armour
64.03 mm
Diameter over insulation
22.1 mm
Diameter over screen
25.43 mm
Nominal Duct Diameter
100 mm
Nominal Screen Area on each core
68.09 mm²
Nominal armour wire diameter
2.5 mm
Nominal diameter over bedding
54.8 mm
Nominal insulation thickness
3.4 mm
Nominal overall diameter
70.7 mm
Number of screen wires (nb x mm Ø)
40 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.265 Ohm/km
Armour DC resistance at 20°C
0.431 Ohm/km
Capacitance (All Main Cores - Screen)
0.368 µF / km
Charging current per phase
0.734 A/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
18.6 W/km
Inductive reactance at 50Hz
0.093 Ohm/km
Insulation resistance at 20°C
6600 MOhm.km
Max. DC resistance of the conductor at 20°C
0.206 Ohm/km
Maximum electric stress
2.2 kV/mm
Permissible short circuit current conductor 1s
14.2 kA
Permissible short circuit current screen 1s
10.1 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.119 Ohm/km
Zero sequence resistance at 20°C
0.699 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pull Tension of Armour
45 kN
Maximum Pull Tension of Conductor
22 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1270 mm
Minimum Bend Radius - Installed
850 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core SWA
Current carrying capacity table (in Amps) - 6.35/11kV Three Core SWAConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
150.0 | 375.0 | 293.0 | 403.0 | 315.0 | 288.0 | 218.0 | 367.0 | 287.0 | 309.0 | 237.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground Direct Buried (3 core) |
Underground ducts (3 core) |