- Products
- Market Solutions & Services
- Insight
- Tools & Resources
- About Nexans Australia
- Search
- Contact us
- Compare
- Sign in
3C 95mm2 Al 6.35/11kV SWA Red
3C 95mm2 Al 6.35/11kV SWA Red
6.35/11kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJJA22AA003JBAA
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, laid-up, PVC bedded, steel wire armoured, PVC sheathed.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
Galvanized steel wires
Colour
Red
Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Material of bedding
PVC
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
610.0 kg/100m
Conductor cross-section
95 mm²
Conductor diameter
11.36 mm
Diameter over armour
57.76 mm
Diameter over insulation
19.3 mm
Diameter over screen
22.62 mm
Nominal Duct Diameter
100 mm
Nominal Screen Area on each core
61.28 mm²
Nominal armour wire diameter
2.5 mm
Nominal diameter over bedding
48.7 mm
Nominal insulation thickness
3.4 mm
Nominal overall diameter
63.8 mm
Number of screen wires (nb x mm Ø)
36 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.41 Ohm/km
Armour DC resistance at 20°C
0.479 Ohm/km
Capacitance (All Main Cores - Screen)
0.311 µF / km
Charging current per phase
0.62 A/km
DC Resistance of the Screen at 20°C
0.3 Ohm/km
Dielectric loss per phase
15.8 W/km
Inductive reactance at 50Hz
0.099 Ohm/km
Insulation resistance at 20°C
7800 MOhm.km
Max. DC resistance of the conductor at 20°C
0.32 Ohm/km
Maximum electric stress
2.3 kV/mm
Permissible short circuit current conductor 1s
9 kA
Permissible short circuit current screen 1s
9.09 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.127 Ohm/km
Zero sequence resistance at 20°C
0.868 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pull Tension of Armour
40 kN
Maximum Pull Tension of Conductor
14 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1150 mm
Minimum Bend Radius - Installed
770 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core SWA
Current carrying capacity table (in Amps) - 6.35/11kV Three Core SWAConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
95.0 | 291.0 | 227.0 | 312.0 | 243.0 | 220.0 | 171.0 | 292.0 | 227.0 | 240.0 | 187.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground Direct Buried (3 core) |
Underground ducts (3 core) |