3.8/6.6kV Three Core SWA
3.8/6.6kV Three Core SWA
3.8.6.6kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XHJP15AA003JBAA
- Country ref. : XHJP15AA003JBAA
- EAN : 99319215367063
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Construction
- Stranded compacted conductor
- Triple extruded conductor screen
- XLPE Insulated and insulation screen
- Copper wire screened
- Steel wire armoured
- PVC sheathed.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
Galvanized steel wires
Conductor material
Copper
Insulation
XLPE
Material of bedding
PVC
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
295.0 kg/100m
Conductor cross-section
16 mm²
Conductor diameter
4.85 mm
Diameter over armour
37.98 mm
Diameter over insulation
11.0 mm
Diameter over screen
14.277 mm
Nominal Duct Diameter
65 mm
Nominal Screen Area on each core
17.02 mm²
Nominal armour wire diameter
2 mm
Nominal diameter over bedding
33.98 mm
Nominal insulation thickness
2.5 mm
Nominal overall diameter
42.6 mm
Number of screen wires (nb x mm Ø)
10 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
1.47 Ohm/km
Armour DC resistance at 20°C
0.857 Ohm/km
Capacitance (All Main Cores - Screen)
0.221 µF / km
Charging current per phase
0.263 A/km
DC Resistance of the Screen at 20°C
1.06 Ohm/km
Dielectric loss per phase
4 W/km
Inductive reactance at 50Hz
0.134 Ohm/km
Insulation resistance at 20°C
11000 MOhm.km
Max. DC resistance of the conductor at 20°C
1.152 Ohm/km
Maximum electric stress
2.1 kV/mm
Permissible short circuit current conductor 1s
2.3 kA
Permissible short circuit current screen 1s
2.52 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.153 Ohm/km
Zero sequence resistance at 20°C
2.576 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pull Tension of Armour
22 kN
Maximum Pull Tension of Conductor
3 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
770 mm
Minimum Bend Radius - Installed
510 mm
Resources
Resources
Current carrying capacity table (in Amps) - 3.8/6.6kV Three Core SWA
Current carrying capacity table (in Amps) - 3.8/6.6kV Three Core SWAConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 103.0 | 0.0 | 110.0 | 0.0 | 78.0 | 0.0 | 112.0 | 0.0 | 89.0 | 0.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground Direct Buried (3 core) |
Underground ducts (3 core) |
Our websites