- Products
- Market Solutions & Services
- Insight
- Tools & Resources
- About Nexans Australia
- Search
- Contact us
- Compare
- Sign in
6.35/11kV Single Core
6.35/11kV Single Core
6.35/11kV XLPE Single Core Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJHP15AA001CXAA
- Country ref. : XJHP15AA001CXAA
- EAN : 99319215235546
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Construction
- Stranded compacted conductors
- Copper wire screen
- PVC sheathed
- Semi-conductive conductor screen
- XLPE insulation
- Semi-conductive insulation screen
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wires / 6mm²
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
59.44 kg/100m
Conductor cross-section
16 mm²
Conductor diameter
4.85 mm
Diameter over insulation
12.81 mm
Diameter over screen
16.11 mm
Nominal Duct Diameter Trefoil Single Way
50 mm
Nominal Duct Diameter in Single Way
65 mm
Nominal Screen Area on each core
15.89 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter
20.2 mm
Number of screen wires (nb x mm Ø)
28 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. at 90 °C - flat formation
1.47 Ohm/km
A.C. Conductor resist. at 90 °C - trefoil formation
1.47 Ohm/km
Capacitance (All Main Cores - Screen)
0.181 µF / km
Charging current per phase
0.362 A/km
DC Resistance of the Screen at 20°C
1.14 Ohm/km
Dielectric loss per phase
8.98 W/km
Inductive reactance at 50Hz - flat touching
0.176 Ohm/km
Inductive reactance at 50Hz - trefoil
0.161 Ohm/km
Inductive reactance at 50Hz and 90°C flat spaced
0.222 Ohm/km
Insulation resistance at 20°C
14000 MOhm.km
Max. DC resistance of the conductor at 20°C
1.152 Ohm/km
Maximum electric stress
2.8 kV/mm
Permissible short circuit current conductor 1s
2.3 kA
Permissible short circuit current screen 1s
2.36 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.094 Ohm/km
Zero sequence resistance at 20°C
2.292 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
1.12 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
360 mm
Minimum Bend Radius - Installed
240 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - solid bond - In Air
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - solid bond - In AirConductor cross-section | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 114.0 | 0.0 | 134.0 | 0.0 | 106.0 | 0.0 | 112.0 | 0.0 | 81.0 | 0.0 |
In air flat touching |
In air flat spaced |
In air touching |
In air spaced from surface |
In air enclosed |
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - solid bond - Underground
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - solid bond - UndergroundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 116.0 | 0.0 | 118.0 | 0.0 | 113.0 | 0.0 | 103.0 | 0.0 | 104.0 | 0.0 | 101.0 | 0.0 | 91.0 | 0.0 |
Underground direct flat touching |
Underground direct flat spaced |
Underground direct touching |
Underground ducts flat touching |
Underground ducts flat spaced |
Underground ducts touching |
Underground ducts |
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - single bond - In Air
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - single bond - In AirConductor cross-section | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 129.0 | 0.0 | 151.0 | 0.0 | 120.0 | 0.0 | 126.0 | 0.0 | 91.0 | 0.0 |
In air flat touching |
In air flat spaced |
In air touching |
In air spaced from surface |
In air enclosed |
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - single bond - Underground
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - single bond - UndergroundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 132.0 | 0.0 | 134.0 | 0.0 | 128.0 | 0.0 | 117.0 | 0.0 | 118.0 | 0.0 | 115.0 | 0.0 | 103.0 | 0.0 |
Underground direct flat touching |
Underground direct flat spaced |
Underground direct touching |
Underground ducts flat touching |
Underground ducts flat spaced |
Underground ducts touching |
Underground ducts |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania