6.35/11kV Single Core
6.35/11kV Single Core
6.35/11kV XLPE Single Core Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJHA27AA001CXAA
Description
Description
Standards
-
InternationalIEC 60228; IEC 60502-2
-
NationalAS/NZS 1125; AS/NZS 1429.1
Construction
- Stranded compacted conductors
- Copper wire screen
- PVC sheathed
- Semi-conductive conductor screen
- XLPE insulation
- Semi-conductive insulation screen
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wires
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
215.0 kg/100m
Conductor cross-section
300 mm²
Conductor diameter
20.1 mm
Diameter over insulation
28.26 mm
Diameter over screen
32.56 mm
Nominal Duct Diameter Trefoil Single Way
63 mm
Nominal Duct Diameter in Single Way
150 mm
Nominal Screen Area on each core
68.71 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter
37.3 mm
Number of screen wires (nb x mm Ø)
48 x 1.35 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. at 90 °C - flat formation
0.129 Ohm/km
A.C. Conductor resist. at 90 °C - trefoil formation
0.13 Ohm/km
Capacitance (All Main Cores - Screen)
0.491 µF / km
Charging current per phase
0.98 A/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
24.9 W/km
Inductive reactance at 50Hz - flat touching
0.12 Ohm/km
Inductive reactance at 50Hz - trefoil
0.105 Ohm/km
Inductive reactance at 50Hz and 90°C flat spaced
0.166 Ohm/km
Insulation resistance at 20°C
4900 MOhm.km
Max. DC resistance of the conductor at 20°C
0.1 Ohm/km
Maximum electric stress
2.1 kV/mm
Permissible short circuit current conductor 1s
28.4 kA
Permissible short circuit current screen 1s
10.19 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.045 Ohm/km
Zero sequence resistance at 20°C
0.363 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
15 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
670 mm
Minimum Bend Radius - Installed
450 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - solid bond - In Air
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - solid bond - In AirConductor cross-section | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
300.0 | 617.0 | 498.0 | 670.0 | 555.0 | 598.0 | 472.0 | 639.0 | 504.0 | 438.0 | 347.0 |
In air flat touching |
In air flat spaced |
In air touching |
In air spaced from surface |
In air enclosed |
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - solid bond - Underground
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - solid bond - UndergroundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
300.0 | 516.0 | 419.0 | 478.0 | 399.0 | 538.0 | 427.0 | 431.0 | 358.0 | 397.0 | 338.0 | 457.0 | 369.0 | 462.0 | 366.0 |
Underground direct flat touching |
Underground direct flat spaced |
Underground direct touching |
Underground ducts flat touching |
Underground ducts flat spaced |
Underground ducts touching |
Underground ducts |
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - single bond - In Air
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - single bond - In AirConductor cross-section | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
300.0 | 757.0 | 529.0 | 911.0 | 627.0 | 694.0 | 483.0 | 741.0 | 516.0 | 510.0 | 356.0 |
In air flat touching |
In air flat spaced |
In air touching |
In air spaced from surface |
In air enclosed |
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - single bond - Underground
Current carrying capacity table (in Amps) - 6.35/11kV Single Core - single bond - UndergroundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
300.0 | 636.0 | 447.0 | 667.0 | 462.0 | 626.0 | 438.0 | 585.0 | 406.0 | 601.0 | 414.0 | 572.0 | 397.0 | 538.0 | 376.0 |
Underground direct flat touching |
Underground direct flat spaced |
Underground direct touching |
Underground ducts flat touching |
Underground ducts flat spaced |
Underground ducts touching |
Underground ducts |
Dealer locator
Waiting…
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania