12.7/22kV Single Core
12.7/22kV Single Core
12.7/22kV XLPE Single Core Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XLHP24AA001CXAA
- Country ref. : XLHP24AA001CXAA
- EAN : 99319215166925
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Construction
- Stranded compacted conductor
- Copper wire screen
- PVC sheath
- Semi-conductive insulation screen
- XLPE insulation
- Semi-conductive conductor screen
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
275.0 kg/100m
Conductor cross-section
150 mm²
Conductor diameter
14.5 mm
Diameter over insulation
26.8 mm
Diameter over screen
31.1 mm
Nominal Duct Diameter Trefoil Single Way
63 mm
Nominal Duct Diameter in Single Way
100 mm
Nominal Screen Area on each core
68.71 mm²
Nominal insulation thickness
5.5 mm
Nominal overall diameter
35.6 mm
Number of screen wires (nb x mm Ø)
48 x 1.35 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. at 90 °C - flat formation
0.159 Ohm/km
A.C. Conductor resist. at 90 °C - trefoil formation
0.159 Ohm/km
Capacitance (All Main Cores - Screen)
0.254 µF / km
Charging current per phase
1.013 A/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
51.5 W/km
Inductive reactance at 50Hz - flat touching
0.138 Ohm/km
Inductive reactance at 50Hz - trefoil
0.123 Ohm/km
Inductive reactance at 50Hz and 90°C flat spaced
0.184 Ohm/km
Insulation resistance at 20°C
9500 MOhm.km
Max. DC resistance of the conductor at 20°C
0.124 Ohm/km
Maximum electric stress
3 kV/mm
Permissible short circuit current conductor 1s
21.4 kA
Permissible short circuit current screen 1s
10.19 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.063 Ohm/km
Zero sequence resistance at 20°C
0.394 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
10.5 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
640 mm
Minimum Bend Radius - Installed
430 mm
Resources
Resources
Current carrying capacity table (in Amps) - 12.7/22kV Single Core - solid bond - Underground
Current carrying capacity table (in Amps) - 12.7/22kV Single Core - solid bond - UndergroundConductor cross-section |
|
|
|
|
|
|
|
|||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
150.0 | 371.0 | 293.0 | 358.0 | 289.0 | 374.0 | 293.0 | 319.0 | 257.0 | 305.0 | 251.0 | 326.0 | 259.0 | 314.0 | 246.0 |
Underground direct flat touching |
Underground direct flat spaced |
Underground direct touching |
Underground ducts flat touching |
Underground ducts flat spaced |
Underground ducts touching |
Underground ducts |
Current carrying capacity table (in Amps) - 12.7/22kV Single Core - solid bond - In Air
Current carrying capacity table (in Amps) - 12.7/22kV Single Core - solid bond - In AirConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
150.0 | 423.0 | 334.0 | 469.0 | 376.0 | 400.0 | 312.0 | 425.0 | 331.0 | 293.0 | 229.0 |
In air flat touching |
In air flat spaced |
In air touching |
In air spaced from surface |
In air enclosed |
Current carrying capacity table (in Amps) - 12.7/22kV Single Core - single bond - Underground
Current carrying capacity table (in Amps) - 12.7/22kV Single Core - single bond - UndergroundConductor cross-section |
|
|
|
|
|
|
|
|||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
150.0 | 439.0 | 303.0 | 451.0 | 310.0 | 430.0 | 296.0 | 400.0 | 275.0 | 407.0 | 280.0 | 391.0 | 269.0 | 361.0 | 249.0 |
Underground direct flat touching |
Underground direct flat spaced |
Underground direct touching |
Underground ducts flat touching |
Underground ducts flat spaced |
Underground ducts touching |
Underground ducts |
Current carrying capacity table (in Amps) - 12.7/22kV Single Core - single bond - In Air
Current carrying capacity table (in Amps) - 12.7/22kV Single Core - single bond - in AirConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
150.0 | 498.0 | 343.0 | 580.0 | 397.0 | 459.0 | 316.0 | 487.0 | 335.0 | 336.0 | 232.0 |
In air flat touching |
In air flat spaced |
In air touching |
In air spaced from surface |
In air enclosed |