6.35/11kV Triplex
6.35/11kV Triplex
6.35/11kV Triplex Individually Screened, Water Blocking Taped/HDPE Sheathed Stranded Conductors, up to 10kA fault level
Read more- Nexans ref. : XJZP23TH003
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, water blocking taped, HDPE sheathed, laid up 'Triplex' cables.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
-
Conductor material
Copper
Insulation
XLPE
Outer sheath
HDPE
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
650.0 kg/100m
Conductor cross-section
120 mm²
Conductor diameter
13.07 mm
Diameter over insulation
21.03 mm
Diameter over screen
25.33 mm
Nominal Duct Diameter
100 mm
Nominal Screen Area on each core
68.71 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter of each phase cable
29.9 mm
Nominal overall diameter of triplex
64.3 mm
Number of screen wires (nb x mm Ø)
48 x 1.35 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.196 Ohm/km
Capacitance (All Main Cores - Screen)
0.346 µF / km
Charging current per phase
0.689 A/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
17.5 W/km
Inductive reactance at 50Hz
0.113 Ohm/km
Insulation resistance at 20°C
7000 MOhm.km
Max. DC resistance of the conductor at 20°C
0.153 Ohm/km
Maximum electric stress
2.2 kV/mm
Permissible short circuit current conductor 1s
17.1 kA
Permissible short circuit current screen 1s
10.19 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.056 Ohm/km
Zero sequence resistance at 20°C
0.417 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
25.2 kN
Usage characteristics
Usage characteristics
Minimum Bending Radius of Cable Bundle During Pulling
970 mm
Minimum Bending Radius of Cable Bundle Set in Position
640 mm
Minimum Bending Radius of Phase Cable During Pulling
750 mm
Minimum Bending Radius of Phase Cable Set in Position
450 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Triplex
Current carrying capacity table (in Amps) - 6.35/11kV TriplexConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
120.0 | 348.0 | 271.0 | 370.0 | 288.0 | 257.0 | 201.0 | 335.0 | 261.0 | 279.0 | 218.0 |
In air touching |
In air spaced from surface |
In air enclosed |
Underground direct touching |
Underground ducts |