6.35/11kV Triplex

Description

Description

Standards

  • Product
    AS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2

Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, water blocking taped, HDPE sheathed, laid up 'Triplex' cables.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Armour type
-
Conductor material
Aluminum
Insulation
XLPE
Outer sheath
HDPE
Screen
Copper wire
Type of conductor
Stranded compacted

Dimensional characteristics

Dimensional characteristics

Approximate weight
230.0 kg/100m
Conductor cross-section
50 mm²
Conductor diameter
8.05 mm
Diameter over insulation
16.01 mm
Diameter over screen
20.31 mm
Nominal Duct Diameter
80 mm
Nominal Screen Area on each core
32.92 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter of each phase cable
24.8 mm
Nominal overall diameter of triplex
53.5 mm
Number of screen wires (nb x mm Ø)
23 x 1.35 mm Ø

Electrical characteristics

Electrical characteristics

A.C. Conductor resist. 50Hz and at 90 °C
0.821 Ohm/km
Capacitance (All Main Cores - Screen)
0.243 µF / km
Charging current per phase
0.486 A/km
DC Resistance of the Screen at 20°C
0.55 Ohm/km
Dielectric loss per phase
12.3 W/km
Inductive reactance at 50Hz
0.134 Ohm/km
Insulation resistance at 20°C
9900 MOhm.km
Max. DC resistance of the conductor at 20°C
0.641 Ohm/km
Maximum electric stress
2.5 kV/mm
Permissible short circuit current conductor 1s
4.7 kA
Permissible short circuit current screen 1s
4.88 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.074 Ohm/km
Zero sequence resistance at 20°C
1.189 Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
7.5 kN

Usage characteristics

Usage characteristics

Minimum Bending Radius of Cable Bundle During Pulling
800 mm
Minimum Bending Radius of Cable Bundle Set in Position
540 mm
Minimum Bending Radius of Phase Cable During Pulling
620 mm
Minimum Bending Radius of Phase Cable Set in Position
370 mm

Resources

Resources

Current carrying capacity table (in Amps) - 6.35/11kV Triplex

Current carrying capacity table (in Amps) - 6.35/11kV Triplex
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al
50.0 201.0 157.0 213.0 166.0 150.0 117.0 204.0 159.0 167.0 130.0
In air touching
In air spaced from surface
In air enclosed
Underground direct touching
Underground ducts

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close