12.7/22kV Triplex
12.7/22kV Triplex
12.7/22kV Triplex Individually Screened, Water Blocking Taped/HDPE Sheathed Stranded Conductors, up to 10kA fault level
Read more- Nexans ref. : XLZA22TH003
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, water blocking taped, HDPE sheathed, laid up 'Triplex' cables.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
-
Conductor material
Aluminum
Insulation
XLPE
Outer sheath
HDPE
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
420.0 kg/100m
Conductor cross-section
95 mm²
Conductor diameter
11.4 mm
Diameter over insulation
23.6 mm
Diameter over screen
27.9 mm
Nominal Duct Diameter
100 mm
Nominal Screen Area on each core
61.5 mm²
Nominal insulation thickness
5.5 mm
Nominal overall diameter of each phase cable
32.7 mm
Nominal overall diameter of triplex
70.4 mm
Number of screen wires (nb x mm Ø)
43 x 1.35 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.41 Ohm/km
Capacitance (All Main Cores - Screen)
0.214 µF / km
Charging current per phase
0.855 A/km
DC Resistance of the Screen at 20°C
0.29 Ohm/km
Dielectric loss per phase
43.4 W/km
Inductive reactance at 50Hz
0.126 Ohm/km
Insulation resistance at 20°C
11000 MOhm.km
Max. DC resistance of the conductor at 20°C
0.32 Ohm/km
Maximum electric stress
3.2 kV/mm
Permissible short circuit current conductor 1s
9 kA
Permissible short circuit current screen 1s
9.13 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.071 Ohm/km
Zero sequence resistance at 20°C
0.613 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
14.25 kN
Usage characteristics
Usage characteristics
Minimum Bending Radius of Cable Bundle During Pulling
1060 mm
Minimum Bending Radius of Cable Bundle Set in Position
700 mm
Minimum Bending Radius of Phase Cable During Pulling
820 mm
Minimum Bending Radius of Phase Cable Set in Position
490 mm
Resources
Resources
Current carrying capacity table (in Amps) - 12.7/22kV Triplex
Current carrying capacity table (in Amps) - 12.7/22kV Triplex| Conductor cross-section |
|
|
|
|
|
|||||
|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 95.0 | 309.0 | 241.0 | 327.0 | 255.0 | 230.0 | 180.0 | 296.0 | 231.0 | 249.0 | 194.0 |
| In air touching |
| In air spaced from surface |
| In air enclosed |
| Underground direct touching |
| Underground ducts |