10mm2 PVC SDI Black Insulation White Sheath 100m
10mm2 PVC SDI Black Insulation White Sheath 100m
10mm2 PVC SDI Black Insulation White Sheath 100m
Read more- Nexans ref. : AABP13A1001WVBK
- EAN : 9322576249630
Description
Description
Standards
-
NationalAS/NZS 1125; AS/NZS 5000.1; AS/NZS 5000.2
Single Core PVC SDI Cable
- Single core, V-90 insulated,
- PVC sheathed to AS/NZS 5000,
- Copper conductors, 90°C.
- 1.0 to 16mm2 450/750V to AS/NZS 5000.2
- Larger sizes; 25 to 630mm2 0.6/1kV to AS/NZS 5000.1 are available on request
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
White / black
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
V-90
Outer sheath
PVC
Type of conductor
Stranded copper
Dimensional characteristics
Dimensional characteristics
Approximate weight
14.3 kg/100m
Cable length
100 m
Conductor cross-section
10 mm²
Nominal insulation thickness
1.0 mm
Nominal outer sheath thickness
0.9 mm
Nominal overall diameter
7.8 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
2.23 Ohm/km
Inductive reactance at 50Hz - flat touching
0.134 Ohm/km
Inductive reactance at 50Hz - trefoil
0.118 Ohm/km
Insulation resistance at 20°C
7.2 MOhm.km
Max. DC resistance of the conductor at 20°C
1.83 Ohm/km
Rated Voltage Uo/U (Um)
450/750 V
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum installation tension
700 N
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
47 mm
Minimum Bend Radius - Installed
31 mm
Resources
Resources
PVC SDI - Current carrying capacity table single phase (in Amps)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰CConductor cross-section | |||||||||
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
10.0 | 69 | 67 | 54 | 54 | 44 | 27 | 94 | 69 | 77 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Undergound Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
PVC SDI - Current carrying capacity table three phase (in Amps)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰CConductor cross-section | |||||||||
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
10.0 | 67 | 58 | 54 | 47 | 37 | 27 | 81 | 59 | 70 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Undergound Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
Dealer locator