120mm2 PVC Building Wire Black

Description

Description

Standards

  • National
    AS/NZS 1125; AS/NZS 5000.1

Single Core Building Wires

  • Single core,
  • 0.6/1kV V-90 insulated,
  • to AS/NZS 5000.1 (unsheathed),
  • Copper conductors, 90°C.

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Colour
Black
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
V-90
Type of conductor
Stranded copper
With Green/Yellow core
No

Dimensional characteristics

Dimensional characteristics

Approximate weight
113.5 kg/100m
Cable length
- m
Conductor cross-section
120 mm²
Neutral conductor section (when smaller)
- mm²
Nominal insulation thickness
1.6 mm
Nominal overall diameter
16.4 mm
Number of cores
1

Electrical characteristics

Electrical characteristics

Conductor AC resistance at 50 Hz
0.188 Ohm/km
Inductive reactance at 50Hz - flat touching
0.102 Ohm/km
Inductive reactance at 50Hz - trefoil
0.087 Ohm/km
Insulation resistance at 20°C
3.6 MOhm.km
Max. DC resistance of the conductor at 20°C
0.153 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid
Maximum Pulling Tension
8.4 kN

Usage characteristics

Usage characteristics

Minimum Bend Radius - During Installation (under Tension)
98 mm
Minimum Bend Radius - Installed
66 mm

Resources

Resources

PVC Insulated - Current carrying capacity table single phase (in Amps)

Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰C
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu
120.0 344.0 321.0 267.0 242.0 193.0 0.0 287.0 316.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Thermal insulation, partially surrounded by thermal insulation
Thermal Insulation, completely surrounded by thermal insulation
Underground ducts A - Undergound Wiring Enclosure
Underground ducts B - Individual Wiring Enclosure

PVC Insulated - Current carrying capacity table three phase (in Amps)

Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰C
Conductor cross-section
mm² Cu Cu Cu Cu Cu Cu Cu Cu
120.0 335.0 287.0 267.0 217.0 173.0 0.0 252.0 283.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Thermal insulation, partially surrounded by thermal insulation
Thermal Insulation, completely surrounded by thermal insulation
Underground ducts A - Undergound Wiring Enclosure
Underground ducts B - Individual Wiring Enclosure

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close