10mm2 PVC Building Wire Red 500m
10mm2 PVC Building Wire Red 500m
10mm2 PVC Building Wire Red
Read more- Nexans ref. : BAAP13A5001AARD
- Country ref. : BAAP13A5001AARD
- EAN : 9319215008499
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 5000.1
Single Core Building Wires
- Single core,
- 0.6/1kV V-90 insulated,
- to AS/NZS 5000.1 (unsheathed),
- Copper conductors, 90°C.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
Red
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
V-90
Type of conductor
Stranded copper
With Green/Yellow core
No
Dimensional characteristics
Dimensional characteristics
Approximate weight
11.1 kg/100m
Cable length
500 m
Conductor cross-section
10 mm²
Neutral conductor section (when smaller)
- mm²
Nominal insulation thickness
1.0 mm
Nominal overall diameter
6.0 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
2.23 Ohm/km
Inductive reactance at 50Hz - flat touching
0.134 Ohm/km
Inductive reactance at 50Hz - trefoil
0.118 Ohm/km
Insulation resistance at 20°C
7.2 MOhm.km
Max. DC resistance of the conductor at 20°C
1.83 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum Pulling Tension
0.7 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
36 mm
Minimum Bend Radius - Installed
24 mm
Resources
Resources
PVC Insulated - Current carrying capacity table single phase (in Amps)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰CConductor cross-section |
|
|
|
|
|
|
|
|
---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
10.0 | 69.0 | 67.0 | 54.0 | 54.0 | 44.0 | 27.0 | 69.0 | 77.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Underground ducts A - Undergound Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
PVC Insulated - Current carrying capacity table three phase (in Amps)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰CConductor cross-section |
|
|
|
|
|
|
|
|
---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
10.0 | 67.0 | 58.0 | 54.0 | 47.0 | 37.0 | 27.0 | 59.0 | 70.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Underground ducts A - Undergound Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |