- Products
- Market Solutions & Services
- Insight
- Tools & Resources
- About Nexans Australia
- Search
- Contact us
- Compare
- Sign in
1mm2 PVC Building Wire White 500m
1mm2 PVC Building Wire White 500m
1mm2 PVC Building Wire White
Read more- Nexans ref. : BAAP02A5001AAWT
- Country ref. : BAAP02A5001AAWT
- EAN : 9319215005054
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 5000.1
Single Core Building Wires
- Single core,
- 0.6/1kV V-90 insulated,
- to AS/NZS 5000.1 (unsheathed),
- Copper conductors, 90°C.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
White
Conductor flexibility
Solid class 1
Conductor material
Copper
Conductor shape
Circular
Insulation
V-90
Type of conductor
Solid copper
With Green/Yellow core
No
Dimensional characteristics
Dimensional characteristics
Approximate weight
1.6 kg/100m
Cable length
500 m
Conductor cross-section
1 mm²
Neutral conductor section (when smaller)
- mm²
Nominal insulation thickness
0.8 mm
Nominal overall diameter
2.8 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
25.8 Ohm/km
Inductive reactance at 50Hz - flat touching
0.184 Ohm/km
Inductive reactance at 50Hz - trefoil
0.168 Ohm/km
Insulation resistance at 20°C
15 MOhm.km
Max. DC resistance of the conductor at 20°C
18.1 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum Pulling Tension
0.07 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
34 mm
Minimum Bend Radius - Installed
22 mm
Resources
Resources
PVC Insulated - Current carrying capacity table single phase (in Amps)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰CConductor cross-section |
|
|
|
|
|
|
|
|
---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
1.0 | 16.0 | 16.0 | 13.0 | 13.0 | 11.0 | 6.0 | 18.0 | 21.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Underground ducts A - Undergound Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
PVC Insulated - Current carrying capacity table three phase (in Amps)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰CConductor cross-section |
|
|
|
|
|
|
|
|
---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
1.0 | 16.0 | 14.0 | 13.0 | 12.0 | 10.0 | 6.0 | 16.0 | 19.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Underground ducts A - Undergound Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |