3C 300mm2 Al 6.35/11kV PVC URD 3kA Black
3C 300mm2 Al 6.35/11kV PVC URD 3kA Black
6.35/11kV Three Core, Individually Screened PVC or PVC/HDPE Sheathed URD
Read more- Nexans ref. : XJMA27AA003CXAA
- EAN : 9319215467906
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, PVC sheathed.
XJM - 3kA Screen Fault Level
XJN - 10kA or Heavy Duty Screened
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Outer sheath
PVC/HDPE
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
515.0 kg/100m
Conductor cross-section
300 mm²
Conductor diameter
20.1 mm
Diameter over insulation
28.26 mm
Diameter over screen
31.56 mm
Nominal Duct Diameter
125 mm
Nominal Screen Area on each core
32.34 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter
75.6 mm
Nominal overall diameter
-
Number of screen wires (nb x mm Ø)
19 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.13 Ohm/km
Capacitance (All Main Cores - Screen)
0.491 µF / km
Charging current per phase
0.98 A/km
DC Resistance of the Screen at 20°C
0.56 Ohm/km
Dielectric loss per phase
24.9 W/km
Inductive reactance at 50Hz
0.091 Ohm/km
Insulation resistance at 20°C
4900 MOhm.km
Max. DC resistance of the conductor at 20°C
0.1 Ohm/km
Maximum electric stress
2.1 kV/mm
Permissible short circuit current conductor 1s
28.4 kA
Rated Voltage Uo/U (Um)
-
Screen fault current carrying capacity for 1 second
4.797 kA
Zero sequence reactance at 50HZ
0.044 Ohm/km
Zero sequence resistance at 20°C
1.778 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
45 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1890 mm
Minimum Bend Radius - Installed
1130 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core
Current carrying capacity table (in Amps) - 6.35/11kV Three CoreConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
300.0 | 594.0 | 462.0 | 645.0 | 501.0 | 442.0 | 344.0 | 560.0 | 437.0 | 470.0 | 366.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground direct buried (3 core) |
Underground ducts (3 core) |
Our websites