3C Cu 6.35/11kV URD PVC Black to Vic Specification
3C Cu 6.35/11kV URD PVC Black to Vic Specification
6.35/11kV Three Core, Individually screened PVC Sheathed URD Copper Conductors to Powercor Specification
Read more- Nexans ref. : XJHP25SUT03CXAA
- Country ref. : XJHP25SUT03CXAA
- EAN : 99319215445495
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, PVC sheathed.
XJM - 3kA Screen Fault Level
XJN - 10kA or Heavy Duty Screened
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wires / 6mm²
Type of conductor
Circular, stranded, class 2
Dimensional characteristics
Dimensional characteristics
Approximate weight
770.0 kg/100m
Conductor cross-section
185 mm²
Conductor diameter
16.1 mm
Diameter over insulation
24.1 mm
Diameter over screen
27.4 mm
Nominal Duct Diameter
100 mm
Nominal Screen Area on each core
42 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter
66.0 mm
Nominal overall diameter
Number of screen wires (nb x mm Ø)
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.128 Ohm/km
Capacitance (All Main Cores - Screen)
0.407 µF / km
Charging current per phase
0.811 A/km
DC Resistance of the Screen at 20°C
- Ohm/km
Dielectric loss per phase
20.6 W/km
Inductive reactance at 50Hz
0.096 Ohm/km
Insulation resistance at 20°C
5900 MOhm.km
Max. DC resistance of the conductor at 20°C
0.099 Ohm/km
Maximum electric stress
2.2 kV/mm
Permissible short circuit current conductor 1s
26.4 kA
Rated Voltage Uo/U (Um)
6.35 / 11 kV
Screen fault current carrying capacity for 1 second
18.8 kA
Zero sequence reactance at 50HZ
- Ohm/km
Zero sequence resistance at 20°C
- Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
25 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1190 mm
Minimum Bend Radius - Installed
790 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core
Current carrying capacity table (in Amps) - 6.35/11kV Three CoreConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
185.0 | 440.0 | 341.0 | 476.0 | 368.0 | 322.0 | 250.0 | 429.0 | 333.0 | 350.0 | 272.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground direct buried (3 core) |
Underground ducts (3 core) |
Our websites