12.7/22kV Three Core SWA
12.7/22kV Three Core SWA
12.7/22kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XLJP23AA003JBAA
- Country ref. : XLJP23AA003JBAA
- EAN : 99319215167670
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Construction
- Stranded compacted conductor
- Triple extruded conductor screen
- Insulation and insulation screen
- Copper wire screen
- Steel wire armoured
- PVC sheathed
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
Galvanized steel wires
Conductor material
Copper
Insulation
XLPE
Material of bedding
PVC
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
1140.0 kg/100m
Conductor cross-section
120 mm²
Conductor diameter
13.07 mm
Diameter over armour
72.61 mm
Diameter over insulation
25.3 mm
Diameter over screen
28.6 mm
Nominal Duct Diameter
125 mm
Nominal Screen Area on each core
68.09 mm²
Nominal armour wire diameter
3.15 mm
Nominal insulation thickness
5.5 mm
Nominal overall diameter
79.6 mm
Number of screen wires (nb x mm Ø)
40 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.196 Ohm/km
Armour DC resistance at 20°C
0.302 Ohm/km
Capacitance (All Main Cores - Screen)
0.236 µF / km
Charging current per phase
0.942 A/km
Conductor to screen capacitance
0.24 mF/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
47.8 W/km
Inductive reactance at 50Hz
0.112 Ohm/km
Insulation resistance at 20°C
10000 MOhm.km
Max. DC resistance of the conductor at 20°C
0.153 Ohm/km
Maximum electric stress
3.1 kV/mm
Permissible short circuit current conductor 1s
17.1 kA
Permissible short circuit current screen 1s
10.1 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.131 Ohm/km
Zero sequence resistance at 20°C
0.577 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pull Tension of Armour
64 kN
Maximum Pull Tension of Conductor
25 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1430 mm
Minimum Bend Radius - Installed
960 mm
Resources
Resources
Current carrying capacity table (in Amps) - 12.7/22kV Three Core SWA
Current carrying capacity table (in Amps) - 12.7/22kV Three Core SWAConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
120.0 | 339.0 | 264.0 | 363.0 | 283.0 | 262.0 | 205.0 | 330.0 | 258.0 | 280.0 | 219.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground Direct Buried (3 core) |
Underground ducts (3 core) |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania