19/33kV Single Core
19/33kV Single Core
19/33kV XLPE Single Core Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XNHP19AA001CXAA
- Country ref. : XNHP19AA001CXAA
- EAN : 99319215168844
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Construction
- Stranded compacted conductor
- Copper wire screen
- PVC sheath
- Semi-conductive insulation screen
- XLPE insulation
- Semi-conductice conductor screen
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
170.0 kg/100m
Conductor cross-section
50 mm²
Conductor diameter
8.0 mm
Diameter over insulation
25.516 mm
Diameter over screen
29.816 mm
Nominal Duct Diameter Trefoil Single Way
63 mm
Nominal Duct Diameter in Single Way
100 mm
Nominal Screen Area on each core
48.67 mm²
Nominal insulation thickness
8.0 mm
Nominal overall diameter
34.3 mm
Nominal overall diameter
-
Number of screen wires (nb x mm Ø)
34 x 1.35 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. at 90 °C - flat formation
0.494 Ohm/km
A.C. Conductor resist. at 90 °C - trefoil formation
0.494 Ohm/km
Capacitance (All Main Cores - Screen)
0.133 µF / km
Charging current per phase
0.801 A/km
DC Resistance of the Screen at 20°C
0.37 Ohm/km
Dielectric loss per phase
60.5 W/km
Inductive reactance at 50Hz - flat touching
0.178 Ohm/km
Inductive reactance at 50Hz - trefoil
0.163 Ohm/km
Inductive reactance at 50Hz and 90°C flat spaced
0.224 Ohm/km
Insulation resistance at 20°C
18000 MOhm.km
Max. DC resistance of the conductor at 20°C
0.387 Ohm/km
Maximum electric stress
4 kV/mm
Permissible short circuit current conductor 1s
7.1 kA
Permissible short circuit current screen 1s
7.22 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.1 Ohm/km
Zero sequence resistance at 20°C
0.759 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
3.5 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
620 mm
Minimum Bend Radius - Installed
410 mm
Resources
Resources
Current carrying capacity table (in Amps) - 19/33kV Single Core - solid bond - In Air
Current carrying capacity table (in Amps) - 19/33kV Single Core - solid bond - In AirConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
50.0 | 224.0 | 175.0 | 250.0 | 197.0 | 210.0 | 163.0 | 221.0 | 172.0 | 160.0 | 125.0 |
In air flat touching |
In air flat spaced |
In air touching |
In air spaced from surface |
In air enclosed |
Current carrying capacity table (in Amps) - 19/33kV Single Core - solid bond - Underground
Current carrying capacity table (in Amps) - 19/33kV Single Core - solid bond - UndergroundConductor cross-section |
|
|
|
|
|
|
|
|||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
50.0 | 208.0 | 162.0 | 209.0 | 164.0 | 205.0 | 159.0 | 187.0 | 147.0 | 186.0 | 148.0 | 185.0 | 145.0 | 174.0 | 135.0 |
Underground direct flat touching |
Underground direct flat spaced |
Underground direct touching |
Underground ducts flat touching |
Underground ducts flat spaced |
Underground ducts touching |
Underground ducts |
Current carrying capacity table (in Amps) - 19/33kV Single Core - single bond - In Air
Current carrying capacity table (in Amps) - 19/33kV Single Core - single bond - In AirConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
50.0 | 256.0 | 176.0 | 289.0 | 198.0 | 238.0 | 164.0 | 250.0 | 172.0 | 182.0 | 125.0 |
In air flat touching |
In air flat spaced |
In air touching |
In air spaced from surface |
In air enclosed |
Current carrying capacity table (in Amps) - 19/33kV Single Core - single bond - Underground
Current carrying capacity table (in Amps) - 19/33kV Single Core - single bond - UndergroundConductor cross-section |
|
|
|
|
|
|
|
|||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
50.0 | 237.0 | 163.0 | 242.0 | 166.0 | 232.0 | 160.0 | 216.0 | 149.0 | 220.0 | 151.0 | 212.0 | 145.0 | 197.0 | 136.0 |
Underground direct flat touching |
Underground direct flat spaced |
Underground direct touching |
Underground ducts flat touching |
Underground ducts flat spaced |
Underground ducts touching |
Underground ducts |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania