150mm2 Al XLPE / PVC SDI Black
150mm2 Al XLPE / PVC SDI Black
150mm2 Al XLPE / PVC SDI Black
Read more- Nexans ref. : BDBA24AA001CXNA
- Country ref. : BDBA24AA001CXNA
- EAN : 99319215280218
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 5000.1
Single core XLPE SDI Cable
- Single core, 0.6/1kV X-90 insulated,
- PVC sheathed to AS/NZS 5000.1,
- Aluminium conductor, 90°C.
Mains; Submains
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
Black
Conductor material
Aluminum
Type of conductor
Circular compacted
Conductor shape
Circular
Conductor flexibility
Class 2
Insulation
X-90
Outer sheath
PVC
Dimensional characteristics
Dimensional characteristics
Approximate weight
60.0 kg/100m
Cable length
- m
Conductor cross-section
150 mm²
Nominal insulation thickness
1.4 mm
Nominal outer sheath thickness
1.6 mm
Nominal overall diameter
20.5 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
0.253 Ohm/km
Inductive reactance at 50Hz - flat touching
0.1 Ohm/km
Inductive reactance at 50Hz - trefoil
0.084 Ohm/km
Insulation resistance at 20°C
240 MOhm.km
Max. DC resistance of the conductor at 20°C
0.206 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum Pull Tension of Conductor
8 kN
Maximum Pulling Tension
2.5 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
245 mm
Minimum Bend Radius - Installed
165 mm
Resources
Resources
XLPE/PVC single core - Current carrying capacity table single phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰CConductor cross-section |
|
|
|
|
|
|
|
|
|
|||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
150.0 | 486.0 | 377.0 | 451.0 | 350.0 | 375.0 | 291.0 | 329.0 | 255.0 | 263.0 | 204.0 | 0.0 | 0.0 | 480.0 | 372.0 | 365.0 | 283.0 | 401.0 | 311.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Underground Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
XLPE/PVC single core - Current carrying capacity table three phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰CConductor cross-section |
|
|
|
|
|
|
|
|
|
|||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
150.0 | 472.0 | 366.0 | 403.0 | 313.0 | 375.0 | 291.0 | 295.0 | 229.0 | 236.0 | 183.0 | 0.0 | 0.0 | 400.0 | 310.0 | 320.0 | 249.0 | 358.0 | 277.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Underground Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |