50mm2 Al XLPE / PVC SDI Black
50mm2 Al XLPE / PVC SDI Black
50mm2 Al XLPE / PVC SDI Black
Read more- Nexans ref. : BDBA19AA001CXNA
- Country ref. : BDBA19AA001CXNA
- EAN : 99319215280072
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 5000.1
Single core XLPE SDI Cable
- Single core, 0.6/1kV X-90 insulated,
- PVC sheathed to AS/NZS 5000.1,
- Aluminium conductor, 90°C.
Mains; Submains
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
Black
Conductor material
Aluminum
Type of conductor
Circular compacted
Conductor shape
Circular
Conductor flexibility
Class 2
Insulation
X-90
Outer sheath
PVC
Dimensional characteristics
Dimensional characteristics
Approximate weight
23.0 kg/100m
Cable length
- m
Conductor cross-section
50 mm²
Nominal insulation thickness
1.0 mm
Nominal outer sheath thickness
1.4 mm
Nominal overall diameter
13.1 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
0.783 Ohm/km
Inductive reactance at 50Hz - flat touching
0.108 Ohm/km
Inductive reactance at 50Hz - trefoil
0.092 Ohm/km
Insulation resistance at 20°C
300 MOhm.km
Max. DC resistance of the conductor at 20°C
0.641 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum Pull Tension of Conductor
2 kN
Maximum Pulling Tension
1.6 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
155 mm
Minimum Bend Radius - Installed
105 mm
Resources
Resources
XLPE/PVC single core - Current carrying capacity table single phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰C| Conductor cross-section |
|
|
|
|
|
|
|
|
|
|||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 50.0 | 228.0 | 177.0 | 216.0 | 167.0 | 176.0 | 136.0 | 166.0 | 129.0 | 133.0 | 103.0 | 0.0 | 0.0 | 255.0 | 198.0 | 189.0 | 147.0 | 211.0 | 164.0 |
| Unenclosed spaced |
| Unenclosed spaced from surface |
| Unenclosed touching |
| Enclosed conduit in air |
| Thermal insulation, partially surrounded by thermal insulation |
| Thermal Insulation, completely surrounded by thermal insulation |
| Buried direct |
| Underground ducts A - Underground Wiring Enclosure |
| Underground ducts B - Individual Wiring Enclosure |
XLPE/PVC single core - Current carrying capacity table three phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰C| Conductor cross-section |
|
|
|
|
|
|
|
|
|
|||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 50.0 | 221.0 | 171.0 | 188.0 | 146.0 | 176.0 | 136.0 | 143.0 | 111.0 | 114.0 | 89.0 | 0.0 | 0.0 | 214.0 | 166.0 | 163.0 | 126.0 | 190.0 | 147.0 |
| Unenclosed spaced |
| Unenclosed spaced from surface |
| Unenclosed touching |
| Enclosed conduit in air |
| Thermal insulation, partially surrounded by thermal insulation |
| Thermal Insulation, completely surrounded by thermal insulation |
| Buried direct |
| Underground ducts A - Underground Wiring Enclosure |
| Underground ducts B - Individual Wiring Enclosure |