XLP 1X70 PC 0.6/1KV PVC

Description

Description

Standards

  • National
    AS/NZS 1125; AS/NZS 5000.1

Single core XLPE SDI Cable

  • Single core, 0.6/1kV X-90 insulated,
  • PVC sheathed to AS/NZS 5000.1,
  • Copper conductor, 90°C.

 

 

Mains; Submains

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Colour
Black
Conductor material
Copper
Type of conductor
Compact copper
Conductor shape
Circular
Conductor flexibility
Class 2
Insulation
X-90
Outer sheath
PVC

Dimensional characteristics

Dimensional characteristics

Approximate weight
73.0 kg/100m
Cable length
500 m
Conductor cross-section
70 mm²
Nominal insulation thickness
1.1 mm
Nominal outer sheath thickness
1.4 mm
Nominal overall diameter
14.7 mm
Number of cores
1

Electrical characteristics

Electrical characteristics

Conductor AC resistance at 50 Hz
0.471 Ohm/km
Inductive reactance at 50Hz - flat touching
0.108 Ohm/km
Inductive reactance at 50Hz - trefoil
0.092 Ohm/km
Insulation resistance at 20°C
270 MOhm.km
Max. DC resistance of the conductor at 20°C
0.268 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid
Maximum Pull Tension of Conductor
5 kN
Maximum Pulling Tension
1.8 kN

Usage characteristics

Usage characteristics

Minimum Bend Radius - During Installation (under Tension)
180 mm
Minimum Bend Radius - Installed
120 mm

Resources

Resources

XLPE/PVC single core - Current carrying capacity table single phase (in Amps)

Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰C
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
70.0 291.0 226.0 273.0 212.0 224.0 174.0 204.0 159.0 164.0 127.0 0.0 0.0 313.0 243.0 233.0 181.0 258.0 200.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Thermal insulation, partially surrounded by thermal insulation
Thermal Insulation, completely surrounded by thermal insulation
Buried direct
Underground ducts A - Underground Wiring Enclosure
Underground ducts B - Individual Wiring Enclosure

XLPE/PVC single core - Current carrying capacity table three phase (in Amps)

Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰C
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
70.0 282.0 219.0 240.0 186.0 224.0 174.0 183.0 142.0 146.0 114.0 0.0 0.0 262.0 203.0 203.0 158.0 232.0 180.0
Unenclosed spaced
Unenclosed spaced from surface
Unenclosed touching
Enclosed conduit in air
Thermal insulation, partially surrounded by thermal insulation
Thermal Insulation, completely surrounded by thermal insulation
Buried direct
Underground ducts A - Underground Wiring Enclosure
Underground ducts B - Individual Wiring Enclosure

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*