XLP 1X25 PC 0.6/1KV PVC
XLP 1X25 PC 0.6/1KV PVC
25mm2 XLPE / PVC SDI Black
Read more- Nexans ref. : BDBC17AA001CXNA
- EAN : 9319215277249
Description
Description
Standards
-
NationalAS/NZS 1125; AS/NZS 5000.1
Single core XLPE SDI Cable
- Single core, 0.6/1kV X-90 insulated,
- PVC sheathed to AS/NZS 5000.1,
- Copper conductor, 90°C.
Mains; Submains
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
Black
Conductor material
Copper
Type of conductor
Compact copper
Conductor shape
Circular
Conductor flexibility
Class 2
Insulation
X-90
Outer sheath
PVC
Dimensional characteristics
Dimensional characteristics
Approximate weight
30.0 kg/100m
Cable length
- m
Conductor cross-section
25 mm²
Nominal insulation thickness
0.9 mm
Nominal outer sheath thickness
1.4 mm
Nominal overall diameter
10.5 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
0.927 Ohm/km
Inductive reactance at 50Hz - flat touching
0.122 Ohm/km
Inductive reactance at 50Hz - trefoil
0.106 Ohm/km
Insulation resistance at 20°C
350 MOhm.km
Max. DC resistance of the conductor at 20°C
0.727 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum Pull Tension of Conductor
2 kN
Maximum Pulling Tension
1.3 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
130 mm
Minimum Bend Radius - Installed
84 mm
Resources
Resources
XLPE/PVC single core - Current carrying capacity table single phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰CConductor cross-section | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
25.0 | 151.0 | 117.0 | 145.0 | 112.0 | 117.0 | 91.0 | 113.0 | 87.0 | 90.0 | 70.0 | 58.0 | 45.0 | 179.0 | 139.0 | 131.0 | 102.0 | 146.0 | 114.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Underground Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
XLPE/PVC single core - Current carrying capacity table three phase (in Amps)
Copper or Aluminium Conductor XLPE Insulation Maximum Conductor Temperature 90⁰CConductor cross-section | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
25.0 | 146.0 | 113.0 | 125.0 | 97.0 | 117.0 | 91.0 | 97.0 | 75.0 | 77.0 | 60.0 | 58.0 | 45.0 | 151.0 | 117.0 | 113.0 | 87.0 | 132.0 | 103.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Underground Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |