NEXANS LFH Single Core 110°C Flexible
NEXANS LFH Single Core 110°C Flexible
Single core flexible copper conductor, 0.6/1kV X-HF-110 insulated, HFS-110-TP sheathed to AS/NZS 5000.1, Low smoke zero halogen insulation and sheath, 110°C continuous
Read moreNexans LFH 10mm2 Cu Flexible 110C
Nexans ref. BZKR08AA001CXNA - Country ref. BZKR08AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 13.4 kg/100m
- Conductor cross-section: 10 mm²
- Nominal overall diameter: 8.6 mm
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Maximum Pull Tension of Conductor: 0 kN
- Maximum Pulling Tension: 0.2 kN
- Minimum Bend Radius - During Installation (under Tension): 52 mm
- Minimum Bend Radius - Installed: 34 mm
Nexans LFH 120mm2 Cu Flexible 110C
Nexans ref. BZKE87AA001CXNA - Country ref. BZKE87AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 116.9 kg/100m
- Conductor cross-section: 120 mm²
- Nominal overall diameter: 20.4 mm
- Max. DC resistance of the conductor at 20°C: 0.161 Ohm/km
- Maximum Pull Tension of Conductor: 2 kN
- Maximum Pulling Tension: 2.4 kN
- Minimum Bend Radius - During Installation (under Tension): 122 mm
- Minimum Bend Radius - Installed: 82 mm
Nexans LFH 150mm2 Cu Flexible 110C
Nexans ref. BZKE88AA001CXNA - Country ref. BZKE88AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 144.4 kg/100m
- Conductor cross-section: 150 mm²
- Nominal overall diameter: 22.5 mm
- Max. DC resistance of the conductor at 20°C: 0.129 Ohm/km
- Maximum Pull Tension of Conductor: 3 kN
- Maximum Pulling Tension: 2.7 kN
- Minimum Bend Radius - During Installation (under Tension): 135 mm
- Minimum Bend Radius - Installed: 90 mm
Nexans LFH 16mm2 Cu Flexible 110C
Nexans ref. BZKR09AA001CXNA - Country ref. BZKR09AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 19.4 kg/100m
- Conductor cross-section: 16 mm²
- Nominal overall diameter: 9.8 mm
- Max. DC resistance of the conductor at 20°C: 1.21 Ohm/km
- Maximum Pull Tension of Conductor: 0 kN
- Maximum Pulling Tension: 0.32 kN
- Minimum Bend Radius - During Installation (under Tension): 59 mm
- Minimum Bend Radius - Installed: 39 mm
Nexans LFH 185mm2 Cu Flexible 110C
Nexans ref. BZKE89AA001CXNA - Country ref. BZKE89AA001CXNA
- Packaging: Cut to length (m)
- Approximate weight: 175.6 kg/100m
- Conductor cross-section: 185 mm²
- Nominal overall diameter: 24.8 mm
- Max. DC resistance of the conductor at 20°C: 0.106 Ohm/km
- Maximum Pull Tension of Conductor: 4 kN
- Maximum Pulling Tension: 2.98 kN
- Minimum Bend Radius - During Installation (under Tension): 149 mm
- Minimum Bend Radius - Installed: 99 mm
Description
Description
Standards
-
ProductAS/NZS 5000.1
-
TestAS/NZS 4507
NEXANS LFH flexible single core cable is part of the Nexans Fire Safety Offer. As a Low Fire Hazard (LFH) range, NEXANS LFH is PVC-free, made with flame retardant compound and reduces toxic smoke emissions in the event of fire, allowing time for safe evacuation.
- 0.6/1kV cables,
- Flexible, X-HF-110 insulated to AS/NZS 5000.1
- HFS-110-TP sheathed to AS/NZS 5000.1
- 110°C continuous
- Low fire hazard - Flame retardant
- PVC-free
- Meets physical property requirements of 125°C XLPO insulation to UL 1581
*Replaces ENVIROLEX® and VERSOLEX® 110 Single Core
RHE-1 to AS/NZ 4507.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
ENVIROLEX® Flexible Single Core 110°C - Current carrying capacity table single phase (in Amps)
Insulation type: R-HF-110, R-E-110 OR X-HF-110
Maximum conductor temperature: 110°C
Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
Conductor cross-section |
|
|
|
|
|
|
|
|
|
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
Conductor cross-section 1.0 |
|||||||||
Conductor cross-section 1.5 |
|||||||||
Conductor cross-section 2.5 |
|||||||||
Conductor cross-section 4.0 |
|||||||||
Conductor cross-section 6.0 |
|||||||||
Conductor cross-section 10.0 |
|||||||||
Conductor cross-section 16.0 |
|||||||||
Conductor cross-section 25.0 |
|||||||||
Conductor cross-section 35.0 |
|||||||||
Conductor cross-section 50.0 |
|||||||||
Conductor cross-section 70.0 |
|||||||||
Conductor cross-section 95.0 |
|||||||||
Conductor cross-section 120.0 |
|||||||||
Conductor cross-section 150.0 |
|||||||||
Conductor cross-section 185.0 |
|||||||||
Conductor cross-section 240.0 |
|||||||||
Conductor cross-section 300.0 |
|||||||||
Conductor cross-section 400.0 |
|||||||||
Conductor cross-section 500.0 |
|||||||||
Conductor cross-section 630.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Enclosed, partially surrounded by thermal insulation |
Enclosed, completely surrounded by thermal insulation |
Buried direct |
Underground Wiring Enclosure |
Individual wiring enclosure |
ENVIROLEX® Flexible Single Core 110°C - Current carrying capacity table three phase (in Amps)
Insulation type: R-HF-110, R-E-110 OR X-HF-110
Maximum conductor temperature: 110°C
Reference ambient temperature: 40°C IN AIR, 25°C IN GROUND
Conductor cross-section |
|
|
|
|
|
|
|
|
|
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
Conductor cross-section 1.0 |
|||||||||
Conductor cross-section 1.5 |
|||||||||
Conductor cross-section 2.5 |
|||||||||
Conductor cross-section 4.0 |
|||||||||
Conductor cross-section 6.0 |
|||||||||
Conductor cross-section 10.0 |
|||||||||
Conductor cross-section 16.0 |
|||||||||
Conductor cross-section 25.0 |
|||||||||
Conductor cross-section 35.0 |
|||||||||
Conductor cross-section 50.0 |
|||||||||
Conductor cross-section 70.0 |
|||||||||
Conductor cross-section 95.0 |
|||||||||
Conductor cross-section 120.0 |
|||||||||
Conductor cross-section 150.0 |
|||||||||
Conductor cross-section 185.0 |
|||||||||
Conductor cross-section 240.0 |
|||||||||
Conductor cross-section 300.0 |
|||||||||
Conductor cross-section 400.0 |
|||||||||
Conductor cross-section 500.0 |
|||||||||
Conductor cross-section 630.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Enclosed, partially surrounded by thermal insulation |
Enclosed, completely surrounded by thermal insulation |
Buried direct |
Underground Wiring Enclosure |
Individual wiring enclosure |