1.0mm2 PVC SDI Red Insulation White Sheath 200m
1.0mm2 PVC SDI Red Insulation White Sheath 200m
1.0mm2 PVC SDI Red Insulation White Sheath 200m
Read more- Nexans ref. : AABP02A2001WTRD
- EAN : 9319215315641
Description
Description
Standards
-
NationalAS/NZS 1125; AS/NZS 5000.1; AS/NZS 5000.2
Single Core PVC SDI Cable
- Single core, V-90 insulated,
- PVC sheathed to AS/NZS 5000,
- Copper conductors, 90°C.
- 1.0 to 16mm2 450/750V to AS/NZS 5000.2
- Larger sizes; 25 to 630mm2 0.6/1kV to AS/NZS 5000.1 are available on request
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
White / red
Conductor flexibility
Solid class 1
Conductor material
Copper
Conductor shape
Circular
Insulation
V-90
Outer sheath
PVC
Type of conductor
Solid, Class 1
Dimensional characteristics
Dimensional characteristics
Approximate weight
2.7 kg/100m
Cable length
200 m
Conductor cross-section
1 mm²
Nominal insulation thickness
0.6 mm
Nominal outer sheath thickness
0.8 mm
Nominal overall diameter
4.0 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
25.8 Ohm/km
Inductive reactance at 50Hz - flat touching
0.184 Ohm/km
Inductive reactance at 50Hz - trefoil
0.168 Ohm/km
Insulation resistance at 20°C
13 MOhm.km
Max. DC resistance of the conductor at 20°C
18.1 Ohm/km
Rated Voltage Uo/U (Um)
450/750 V
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum installation tension
70 N
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
24 mm
Minimum Bend Radius - Installed
16 mm
Resources
Resources
PVC SDI - Current carrying capacity table single phase (in Amps)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰CConductor cross-section | |||||||||
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
1.0 | 16 | 16 | 13 | 13 | 11 | 6 | 24 | 18 | 21 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Undergound Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
PVC SDI - Current carrying capacity table three phase (in Amps)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰CConductor cross-section | |||||||||
---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
1.0 | 16 | 14 | 13 | 12 | 10 | 6 | 21 | 16 | 19 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Buried direct |
Underground ducts A - Undergound Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |