- Products
- Market Solutions & Services
- Insight
- Tools & Resources
- About Nexans Australia
- Search
- Contact us
- Compare
- Sign in
4mm2 PVC Building Wire Red 100m
4mm2 PVC Building Wire Red 100m
4mm2 PVC Building Wire Red
Read more- Nexans ref. : BAAP09A1001AARD
- EAN : 9319215007546
Description
Description
Standards
-
NationalAS/NZS 1125; AS/NZS 5000.1
Single Core Building Wires
- Single core,
- 0.6/1kV V-90 insulated,
- to AS/NZS 5000.1 (unsheathed),
- Copper conductors, 90°C.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Colour
Red
Conductor flexibility
Class 2
Conductor material
Copper
Conductor shape
Circular
Insulation
V-90
Type of conductor
Stranded copper
With Green/Yellow core
No
Dimensional characteristics
Dimensional characteristics
Approximate weight
5.1 kg/100m
Cable length
100 m
Conductor cross-section
4 mm²
Neutral conductor section (when smaller)
- mm²
Nominal insulation thickness
1.0 mm
Nominal overall diameter
4.5 mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
5.61 Ohm/km
Inductive reactance at 50Hz - flat touching
0.152 Ohm/km
Inductive reactance at 50Hz - trefoil
0.137 Ohm/km
Insulation resistance at 20°C
10 MOhm.km
Max. DC resistance of the conductor at 20°C
4.61 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Rigid
Maximum Pulling Tension
0.28 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
27 mm
Minimum Bend Radius - Installed
18 mm
Resources
Resources
PVC Insulated - Current carrying capacity table single phase (in Amps)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰CConductor cross-section | ||||||||
---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
4.0 | 40.0 | 39.0 | 31.0 | 32.0 | 25.0 | 16.0 | 41.0 | 47.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Underground ducts A - Undergound Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
PVC Insulated - Current carrying capacity table three phase (in Amps)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75⁰CConductor cross-section | ||||||||
---|---|---|---|---|---|---|---|---|
mm² | Cu | Cu | Cu | Cu | Cu | Cu | Cu | Cu |
4.0 | 38.0 | 33.0 | 31.0 | 28.0 | 23.0 | 16.0 | 36.0 | 43.0 |
Unenclosed spaced |
Unenclosed spaced from surface |
Unenclosed touching |
Enclosed conduit in air |
Thermal insulation, partially surrounded by thermal insulation |
Thermal Insulation, completely surrounded by thermal insulation |
Underground ducts A - Undergound Wiring Enclosure |
Underground ducts B - Individual Wiring Enclosure |
Dealer locator
Waiting…
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania