Type AAAC/1120
Type AAAC/1120
Aluminium alloy 1120 conductors manufactured to AS 1531
Read more- Nexans ref. : Selenium
- EAN : 9319215138403
Description
Description
The wires in all bare conductors are stranded concentrically with successive layers having an opposite direction of lay, the outermost layer being right-handed. When required, a larger central wire (king-wire) is included in a conductor. The diameter of this wire is based on conductor design considerations and is usually 5% greater than the surrounding wires. The incorporation of a king wire is often an advantage for ACSR type conductors, as it ensures that the surrounding layer of wires fits firmly on the central wire.
Note Current ratings are based on the following conditions
- Conductor temperature rise above ambient of 40°C
- Ambient air temperature of 35°C for summer noon or 10°C for winter night
- Direct solar radiation intensity of 1000W/m² for summer noon or zero for winter night
- Diffuse solar radiation intensity of 100W/m² for summer noon or zero for winter night
- Ground reflectance of 0.2
- Emissivity of 0.5 for rural weathered conductor or 0.85 for industrial weathered conductor
- Solar absorption coefficient of 0.5 for rural weathered or 0.85 for industrial weathered conductor
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
aluminum alloy
Dimensional characteristics
Dimensional characteristics
Approximate weight
1400 kg/km
Conductor cross-section
506 mm²
Nominal overall diameter
29.3 mm
Stranding (No./mm)
61/3.25
Stranding No./mm Steel
-
Electrical characteristics
Electrical characteristics
Conductor AC resistance at 50 Hz
0.073 Ohm/km
Inductive reactance at 50Hz
0.206 Ohm/km
Max. DC resistance of the conductor at 20°C
0.059 Ohm/km
Rated Voltage Uo/U (Um)
-
Mechanical characteristics
Mechanical characteristics
Calculated breaking load
114.0 kN
Elongation coefficient
23 10E-6/°C
Final modulus of elasticity (MPA)
64000
Resources
Resources
Type AAAC/1120 - Continuous Current Carrying Capacity in Amps - Rural weathered
Conductor cross-section | ||||||
---|---|---|---|---|---|---|
mm² | Al | Al | Al | Al | Al | Al |
506.0 | 762 | 1120 | 1357 | 518 | 949 | 1172 |
Winter night - Still air |
Winter night - 1m/s wind |
Winter night - 2m/s wind |
Summer noon - Still air |
Summer noon - 1m/s wind |
Summer noon - 2m/s wind |
Type AAAC/1120 - Continuous Current Carrying Capacity in Amps - Industrial weathered
Conductor cross-section | ||||||
---|---|---|---|---|---|---|
mm² | Al | Al | Al | Al | Al | Al |
506.0 | 838 | 1173 | 1401 | 446 | 912 | 1142 |
Winter night - Still air |
Winter night - 1m/s wind |
Winter night - 2m/s wind |
Summer noon - Still air |
Summer noon - 1m/s wind |
Summer noon - 2m/s wind |