3C 95mm2 Al 6.35/11kV PVC URD 10kA Black
3C 95mm2 Al 6.35/11kV PVC URD 10kA Black
6.35/11kV Three Core, Individually Screened PVC or PVC/HDPE Sheathed URD
Read more- Nexans ref. : XJNA22AA003CXAA
- Country ref. : XJNA22AA003CXAA
- EAN : 99319215224717
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, PVC sheathed.
XJM - 3kA Screen Fault Level
XJN - 10kA or Heavy Duty Screened
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Outer sheath
PVC/HDPE
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
285.0 kg/100m
Conductor cross-section
95 mm²
Conductor diameter
11.36 mm
Diameter over insulation
19.32 mm
Diameter over screen
22.62 mm
Nominal Duct Diameter
80 mm
Nominal Screen Area on each core
61.28 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter
55.1 mm
Nominal overall diameter
-
Number of screen wires (nb x mm Ø)
36 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.41 Ohm/km
Capacitance (All Main Cores - Screen)
0.311 µF / km
Charging current per phase
0.62 A/km
DC Resistance of the Screen at 20°C
0.3 Ohm/km
Dielectric loss per phase
15.8 W/km
Inductive reactance at 50Hz
0.099 Ohm/km
Insulation resistance at 20°C
7800 MOhm.km
Max. DC resistance of the conductor at 20°C
0.32 Ohm/km
Maximum electric stress
2.3 kV/mm
Permissible short circuit current conductor 1s
9 kA
Rated Voltage Uo/U (Um)
-
Screen fault current carrying capacity for 1 second
9.089 kA
Zero sequence reactance at 50HZ
0.058 Ohm/km
Zero sequence resistance at 20°C
1.206 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
14.25 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1380 mm
Minimum Bend Radius - Installed
830 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core
Current carrying capacity table (in Amps) - 6.35/11kV Three Core| Conductor cross-section |
|
|
|
|
|
|||||
|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 95.0 | 295.0 | 228.0 | 317.0 | 245.0 | 220.0 | 171.0 | 299.0 | 231.0 | 242.0 | 188.0 |
| In air touching (3 core) |
| In air spaced (3 core) |
| In air enclosed (3 core) |
| Underground direct buried (3 core) |
| Underground ducts (3 core) |