- Products
- Market Solutions & Services
- Insight
- Tools & Resources
- About Nexans Australia
- Search
- Contact us
- Compare
- Sign in
3C 35mm2 Al 6.35/11kV PVC Black
3C 35mm2 Al 6.35/11kV PVC Black
6.35/11kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJHA18AA003CXAA
- Country ref. : XJHA18AA003CXAA
- EAN : 9319215451011
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Construction
- Stranded compacted conductors
- Semi-conductive insulation screen
- Copper wire screen
- XLPE insulation
- Semi-conductive conductor screen
- PVC sheath
- Fillers
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
165.0 kg/100m
Conductor cross-section
35 mm²
Conductor diameter
6.91 mm
Diameter over insulation
14.87 mm
Diameter over screen
18.17 mm
Nominal Duct Diameter
65 mm
Nominal Screen Area on each core
23.83 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter
44.6 mm
Number of screen wires (nb x mm Ø)
14 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
1.11 Ohm/km
Capacitance (All Main Cores - Screen)
0.22 µF / km
Charging current per phase
0.439 A/km
DC Resistance of the Screen at 20°C
0.76 Ohm/km
Dielectric loss per phase
11.1 W/km
Inductive reactance at 50Hz
0.117 Ohm/km
Insulation resistance at 20°C
11000 MOhm.km
Max. DC resistance of the conductor at 20°C
0.868 Ohm/km
Maximum electric stress
2.5 kV/mm
Permissible short circuit current conductor 1s
3.3 kA
Permissible short circuit current screen 1s
3.53 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.078 Ohm/km
Zero sequence resistance at 20°C
3.14 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
5.25 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
800 mm
Minimum Bend Radius - Installed
540 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core
Current carrying capacity table (in Amps) - 6.35/11kV Three Core| Conductor cross-section |
|
|
|
|
|
|||||
|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 35.0 | 162.0 | 126.0 | 173.0 | 135.0 | 120.0 | 93.0 | 173.0 | 134.0 | 136.0 | 106.0 |
| In air touching (3 core) |
| In air spaced (3 core) |
| In air enclosed (3 core) |
| Underground direct buried (3 core) |
| Underground ducts (3 core) |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania