3C 400mm2 Al 6.35/11kV SWA Red
3C 400mm2 Al 6.35/11kV SWA Red
6.35/11kV Three Core, Individually Screened and PVC Sheathed Stranded Conductors up to 10kA fault level
Read more- Nexans ref. : XJJA28AA003JBAA
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, laid-up, PVC bedded, steel wire armoured, PVC sheathed.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
Galvanized steel wires
Colour
Red
Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Material of bedding
PVC
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
1290.0 kg/100m
Conductor cross-section
400 mm²
Conductor diameter
22.95 mm
Diameter over armour
86.06 mm
Diameter over insulation
31.1 mm
Diameter over screen
34.61 mm
Nominal Duct Diameter
150 mm
Nominal Screen Area on each core
68.09 mm²
Nominal armour wire diameter
3.15 mm
Nominal diameter over bedding
74.6 mm
Nominal insulation thickness
3.4 mm
Nominal overall diameter
94.1 mm
Number of screen wires (nb x mm Ø)
40 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.102 Ohm/km
Armour DC resistance at 20°C
0.254 Ohm/km
Capacitance (All Main Cores - Screen)
0.548 µF / km
Charging current per phase
1.094 A/km
DC Resistance of the Screen at 20°C
0.27 Ohm/km
Dielectric loss per phase
27.8 W/km
Inductive reactance at 50Hz
0.083 Ohm/km
Insulation resistance at 20°C
4400 MOhm.km
Max. DC resistance of the conductor at 20°C
0.078 Ohm/km
Maximum electric stress
2.1 kV/mm
Permissible short circuit current conductor 1s
37.8 kA
Permissible short circuit current screen 1s
10.1 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.106 Ohm/km
Zero sequence resistance at 20°C
0.468 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pull Tension of Armour
76 kN
Maximum Pull Tension of Conductor
60 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1690 mm
Minimum Bend Radius - Installed
1130 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Three Core SWA
Current carrying capacity table (in Amps) - 6.35/11kV Three Core SWAConductor cross-section |
|
|
|
|
|
|||||
---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
400.0 | 629.0 | 508.0 | 682.0 | 550.0 | 467.0 | 378.0 | 579.0 | 469.0 | 490.0 | 397.0 |
In air touching (3 core) |
In air spaced (3 core) |
In air enclosed (3 core) |
Underground Direct Buried (3 core) |
Underground ducts (3 core) |