6.35/11kV URD Triplex

Description

Description

Standards

  • Product
    AS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2

Aluminium conductors, triple extruded conductor screen, insulation and insulation screen, copper wire screened, water blocking taped, HDPE sheathed, laid up 'Triplex' cables.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Armour type
-
Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Outer sheath
HDPE
Screen
Copper wire
Type of conductor
Stranded compacted

Dimensional characteristics

Dimensional characteristics

Approximate weight
480.0 kg/100m
Conductor cross-section
300 mm²
Conductor diameter
20.1 mm
Diameter over insulation
28.26 mm
Diameter over screen
31.56 mm
Nominal Duct Diameter
100 mm
Nominal Screen Area on each core
20.43 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter of each phase cable
36.7 mm
Nominal overall diameter of triplex
79.1 mm
Number of screen wires (nb x mm Ø)
36 x 0.85 mm Ø

Electrical characteristics

Electrical characteristics

A.C. Conductor resist. 50Hz and at 90 °C
0.13 Ohm/km
Capacitance (All Main Cores - Screen)
0.491 µF / km
Charging current per phase
0.98 A/km
DC Resistance of the Screen at 20°C
0.88 Ohm/km
Dielectric loss per phase
24.9 W/km
Inductive reactance at 50Hz
0.099 Ohm/km
Insulation resistance at 20°C
4900 MOhm.km
Max. DC resistance of the conductor at 20°C
0.1 Ohm/km
Maximum electric stress
2.1 kV/mm
Permissible short circuit current conductor 1s
28.4 kA
Permissible short circuit current screen 1s
3.03 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.044 Ohm/km
Zero sequence resistance at 20°C
0.986 Ohm/km

Mechanical characteristics

Mechanical characteristics

Maximum Pulling Tension
45 kN

Usage characteristics

Usage characteristics

Minimum Bending Radius of Cable Bundle During Pulling
1190 mm
Minimum Bending Radius of Cable Bundle Set in Position
790 mm
Minimum Bending Radius of Phase Cable During Pulling
920 mm
Minimum Bending Radius of Phase Cable Set in Position
550 mm

Resources

Resources

Current carrying capacity table (in Amps) - 6.35/11kV URD Triplex

Current carrying capacity table (in Amps) - 6.35/11kV URD Triplex
Conductor cross-section
mm² Al Al Al Al Al
300.0 483.0 516.0 355.0 438.0 375.0
In air touching
In air spaced from surface
In air enclosed
Underground direct touching
Underground ducts

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close