6.35/11kV URD Triplex
6.35/11kV URD Triplex
6.35/11kV URD Triplex Individually Screened, Water Blocking Taped/HDPE Sheathed Aluminium Conductors, up to 3kA fault level
Read more- Nexans ref. : XJZA22TJ003
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Aluminium conductors, triple extruded conductor screen, insulation and insulation screen, copper wire screened, water blocking taped, HDPE sheathed, laid up 'Triplex' cables.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
-
Conductor flexibility
Class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Outer sheath
HDPE
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
250.0 kg/100m
Conductor cross-section
95 mm²
Conductor diameter
11.36 mm
Diameter over insulation
19.32 mm
Diameter over screen
22.62 mm
Nominal Duct Diameter
80 mm
Nominal Screen Area on each core
20.43 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter of each phase cable
27.2 mm
Nominal overall diameter of triplex
58.5 mm
Number of screen wires (nb x mm Ø)
36 x 0.85 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.41 Ohm/km
Capacitance (All Main Cores - Screen)
0.311 µF / km
Charging current per phase
0.62 A/km
DC Resistance of the Screen at 20°C
0.89 Ohm/km
Dielectric loss per phase
15.8 W/km
Inductive reactance at 50Hz
0.116 Ohm/km
Insulation resistance at 20°C
7800 MOhm.km
Max. DC resistance of the conductor at 20°C
0.32 Ohm/km
Maximum electric stress
2.3 kV/mm
Permissible short circuit current conductor 1s
9 kA
Permissible short circuit current screen 1s
3.03 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.058 Ohm/km
Zero sequence resistance at 20°C
1.206 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
14.25 kN
Usage characteristics
Usage characteristics
Minimum Bending Radius of Cable Bundle During Pulling
880 mm
Minimum Bending Radius of Cable Bundle Set in Position
590 mm
Minimum Bending Radius of Phase Cable During Pulling
680 mm
Minimum Bending Radius of Phase Cable Set in Position
410 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV URD Triplex
Current carrying capacity table (in Amps) - 6.35/11kV URD TriplexConductor cross-section |
|
|
|
|
|
---|---|---|---|---|---|
mm² | Al | Al | Al | Al | Al |
95.0 | 237.0 | 252.0 | 172.0 | 234.0 | 190.0 |
In air touching |
In air spaced from surface |
In air enclosed |
Underground direct touching |
Underground ducts |