6.35/11kV Triplex
6.35/11kV Triplex
6.35/11kV Triplex Individually Screened, Water Blocking Taped/HDPE Sheathed Stranded Conductors, up to 10kA fault level
Read more- Nexans ref. : XJZP22TH003
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, water blocking taped, HDPE sheathed, laid up 'Triplex' cables.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
-
Conductor material
Copper
Insulation
XLPE
Outer sheath
HDPE
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
565.0 kg/100m
Conductor cross-section
95 mm²
Conductor diameter
11.49 mm
Diameter over insulation
19.45 mm
Diameter over screen
23.75 mm
Nominal Duct Diameter
80 mm
Nominal Screen Area on each core
68.71 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter of each phase cable
28.3 mm
Nominal overall diameter of triplex
60.9 mm
Number of screen wires (nb x mm Ø)
48 x 1.35 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.247 Ohm/km
Capacitance (All Main Cores - Screen)
0.314 µF / km
Charging current per phase
0.626 A/km
DC Resistance of the Screen at 20°C
0.26 Ohm/km
Dielectric loss per phase
15.9 W/km
Inductive reactance at 50Hz
0.117 Ohm/km
Insulation resistance at 20°C
7700 MOhm.km
Max. DC resistance of the conductor at 20°C
0.193 Ohm/km
Maximum electric stress
2.3 kV/mm
Permissible short circuit current conductor 1s
13.6 kA
Permissible short circuit current screen 1s
10.19 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.059 Ohm/km
Zero sequence resistance at 20°C
0.457 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
19.95 kN
Usage characteristics
Usage characteristics
Minimum Bending Radius of Cable Bundle During Pulling
910 mm
Minimum Bending Radius of Cable Bundle Set in Position
610 mm
Minimum Bending Radius of Phase Cable During Pulling
710 mm
Minimum Bending Radius of Phase Cable Set in Position
420 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Triplex
Current carrying capacity table (in Amps) - 6.35/11kV Triplex| Conductor cross-section |
|
|
|
|
|
|||||
|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 95.0 | 302.0 | 236.0 | 321.0 | 251.0 | 226.0 | 176.0 | 296.0 | 231.0 | 246.0 | 192.0 |
| In air touching |
| In air spaced from surface |
| In air enclosed |
| Underground direct touching |
| Underground ducts |