6.35/11kV Triplex
6.35/11kV Triplex
6.35/11kV Triplex Individually Screened, Water Blocking Taped/HDPE Sheathed Stranded Conductors, up to 10kA fault level
Read more- Nexans ref. : XJZP20TH003
Description
Description
Standards
-
ProductAS/NZS 1125; AS/NZS 1429.1; IEC 60228; IEC 60502-2
Stranded compacted conductor, triple extruded conductor screen, insulation and insulation screen, copper wire screened, water blocking taped, HDPE sheathed, laid up 'Triplex' cables.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Armour type
-
Conductor material
Copper
Insulation
XLPE
Outer sheath
HDPE
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
480.0 kg/100m
Conductor cross-section
70 mm²
Conductor diameter
9.6 mm
Diameter over insulation
17.56 mm
Diameter over screen
22.56 mm
Nominal Duct Diameter
80 mm
Nominal Screen Area on each core
68.09 mm²
Nominal insulation thickness
3.4 mm
Nominal overall diameter of each phase cable
27.1 mm
Nominal overall diameter of triplex
58.4 mm
Number of screen wires (nb x mm Ø)
30 x 1.70 mm Ø
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. 50Hz and at 90 °C
0.342 Ohm/km
Capacitance (All Main Cores - Screen)
0.275 µF / km
Charging current per phase
0.549 A/km
DC Resistance of the Screen at 20°C
0.27 Ohm/km
Dielectric loss per phase
13.9 W/km
Inductive reactance at 50Hz
0.129 Ohm/km
Insulation resistance at 20°C
8800 MOhm.km
Max. DC resistance of the conductor at 20°C
0.268 Ohm/km
Maximum electric stress
2.4 kV/mm
Permissible short circuit current conductor 1s
10 kA
Permissible short circuit current screen 1s
10.1 kA
Rated Voltage Uo/U (Um)
-
Zero sequence reactance at 50HZ
0.069 Ohm/km
Zero sequence resistance at 20°C
0.534 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
14.7 kN
Usage characteristics
Usage characteristics
Minimum Bending Radius of Cable Bundle During Pulling
880 mm
Minimum Bending Radius of Cable Bundle Set in Position
580 mm
Minimum Bending Radius of Phase Cable During Pulling
680 mm
Minimum Bending Radius of Phase Cable Set in Position
410 mm
Resources
Resources
Current carrying capacity table (in Amps) - 6.35/11kV Triplex
Current carrying capacity table (in Amps) - 6.35/11kV Triplex| Conductor cross-section |
|
|
|
|
|
|||||
|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 70.0 | 251.0 | 194.0 | 266.0 | 206.0 | 184.0 | 143.0 | 249.0 | 194.0 | 204.0 | 159.0 |
| In air touching |
| In air spaced from surface |
| In air enclosed |
| Underground direct touching |
| Underground ducts |